Voice, Data, and Premise Wire Overall Shield/Multiple Conductor UL Type CMR, CL3R, 75C
Wire Gauge (AWG) | No. of Conductors | Conductor Stranding | Insulation Thickness | Wire Thickness | Approximate Lbs. per 1000ft |
22 | 2 | 7BC | .015 | .13 | 12 |
22 | 3 | 7BC | .015 | .14 | 16 |
22 | 4 | 7BC | .015 | .15 | 20 |
22 | 6 | 7BC | .015 | .17 | 26 |
22 | 8 | 7BC | .015 | .20 | 31 |
22 | 12 | 7BC | .015 | .23 | 42 |
20 | 2 | 7BC | .015 | .15 | 17 |
20 | 3 | 7BC | .015 | .15 | 21 |
20 | 4 | 7BC | .015 | .17 | 25 |
18 | 2 | 7BC | .015 | .16 | 21 |
18 | 3 | 7BC | .015 | .17 | 28 |
18 | 4 | 7BC | .015 | .19 | 35 |
18 | 6 | 7BC | .015 | .23 | 50 |
18 | 8 | 7BC | .015 | .25 | 63 |
18 | 12 | 7BC | .015 | .30 | 90 |
16 | 2 | 19BC | .015 | .19 | 29 |
16 | 3 | 19BC | .015 | .20 | 39 |
16 | 4 | 19BC | .015 | .22 | 50 |
14 | 2 | 19BC | .015 | .25 | 46 |
14 | 3 | 19BC | .015 | .25 | 61 |
14 | 4 | 19BC | .015 | .27 | 79 |
● Used in remote control signaling, power-limited circuits, security, intercom, public address, sound, and audio systems. ● Offers protection from electrostatic interference. ● Conductors are soft bare annealed copper per ASTM B-3. ● Insulation is semi-rigid PVC. ● Jacket is gray PVC with a ripcord applied longitudinally under the jacket. ●Additional Standards: 22AWG-16AWG: UL standard 13, NEC Article 725 Type CL3R and Ul Standard 444, NEC Article 800 Type CMR; – UL stadard 13, NEC Article 725 Type CL3R.
Voice, Data, and Premise Wire Non-shielded/Multiple Conductor UL Type CMR, CL3R, 75C
Wire Gauge (AWG) | No. of Conductors | Conductor Stranding | Insulation Thickness | Wire Thickness | Approximate Lbs. per 1000ft |
22 | 2 | 7BC | .008 | .12 | 9 |
22 | 3 | 7BC | .008 | .14 | 13 |
22 | 4 | 7BC | .008 | .16 | 17 |
22 | 6 | 7BC | .008 | .17 | 22 |
22 | 8 | 7BC | .008 | .18 | 27 |
22 | 12 | 7BC | .008 | .22 | 42 |
20 | 2 | 7BC | .008 | .13 | 11 |
20 | 3 | 7BC | .008 | .13 | 18 |
20 | 4 | 7BC | .008 | .14 | 22 |
18 | 2 | 7BC | .009 | .16 | 18 |
18 | 3 | 7BC | .009 | .17 | 24 |
18 | 4 | 7BC | .009 | .18 | 31 |
18 | 6 | 7BC | .009 | .23 | 46 |
18 | 8 | 7BC | .009 | .25 | 59 |
18 | 12 | 7BC | .009 | .29 | 86 |
16 | 2 | 19BC | .009 | .18 | 26 |
16 | 3 | 19BC | .009 | .19 | 35 |
16 | 4 | 19BC | .009 | .21 | 47 |
14 | 2 | 19BC | .013 | .22 | 41 |
14 | 3 | 19BC | .013 | .24 | 55 |
14 | 4 | 19BC | .013 | .26 | 72 |
12 | 2 | 19BC | .013 | .26 | 57 |
● Used in remote control signaling, power-limited circuits, security, intercom, public address, sound, and audio systems. ● Offers protection from electrostatic interference. ● Conductors are soft bare annealed copper per ASTM B-3. ● Insulation is semi-rigid PVC. ● Jacket is gray PVC with a ripcord applied longitudinally under the jacket. ● Additional Standards: 22AWG-16AWG: UL standard 13, NEC Article 725 Type CL3R and Ul Standard 444, NEC Article 800 Type CMR; – UL stadard 13, NEC Article 725 Type CL3R.